| Technical data |
SCT5564 |
| Measuring range differential current (IΔn) |
0…0.4 A and 0…2 A, DC-100 kHz, type B/B+ |
| Technology |
fluxgate current measurement technology |
| Transformer opening |
70 mm |
| Primary current |
100 A (IΔn = 30 mA) or 300 A (IΔn ≥ 100 mA) |
| Permissible primary current frequency range |
0…400 Hz |
| Secondary current |
4…20 mA |
| Rated power |
15 VA |
| Update interval |
1 ms (1 ksps) |
| Measurement error/ uncertainty |
typ. < ±2.0 % relative to full scale value, see documentation |
| Output relay |
max. 30 V and 1 A AC/DC |
| Rated voltage |
690 V |
| Power supply |
24 V DC (-10 %/+15 %) |
| Dimensions (W x H x D) |
151.3 mm x 161 mm x 83.4 mm |
| Special features |
Test button for triggering a test routine, can also be triggered via external DO, EN/IEC 62020-1:2020. |
| Operating/storage temperature |
-20…+55 °C/-40…+85 °C |
| Approvals/markings |
CE |