Technical data |
SCT5564 |
Measuring range differential current (IΔn) |
0…0.4 A and 0…2 A, DC-100 kHz, type B/B+ |
Technology |
fluxgate current measurement technology |
Transformer opening |
70 mm |
Primary current |
100 A (IΔn = 30 mA) or 300 A (IΔn ≥ 100 mA) |
Permissible primary current frequency range |
0…400 Hz |
Secondary current |
4…20 mA |
Rated power |
15 VA |
Update interval |
1 ms (1 ksps) |
Measurement error/ uncertainty |
typ. < ±2.0 % relative to full scale value, see documentation |
Output relay |
max. 30 V and 1 A AC/DC |
Rated voltage |
690 V |
Power supply |
24 V DC (-10 %/+15 %) |
Dimensions (W x H x D) |
151.3 mm x 161 mm x 83.4 mm |
Special features |
Test button for triggering a test routine, can also be triggered via external DO, EN/IEC 62020-1:2020. |
Operating/storage temperature |
-20…+55 °C/-40…+85 °C |
Approvals/markings |
CE |